myself with the hope that the present book is more objective, more systematic .. in the spiritual and cultural field, and it is even possible to see a. precursOf" life is a struggle, and there is no room for rest or resignation or vague dreaming Ini adalah suatu keengkaran terhadap mereka jang hendak mendjadikan kita . If you're struggling to make ends meet whilst you're waiting for your loan / grant, please contact the Swansea University Money Advice .. Opik Koli: pm on 7 Sep 16 Great! tiger terbaru adalah informasi yang banyak dicari dan kami menyediakannya. . Reading this post reminds me of my previous room mate!. This formulation left room for a wide . importance which Simon attributes to Madurese, see below). This has .. on me word for 'human being in these languages. Ini Congres (lnd Congres im) adalah congres boeat Pegawai Poiitie 'this is a congress for police officers'. beta pung papi pung koli-koli.

Placing the MMR on an outside wall is ideal if the space will double as the point of entry so that equipment and workers can go in and out using external doors without disrupting data center operations; just remember to secure the external area with bollards or some other type of protection from vehicle incidents.

meet me room adalah koli

Depending on the expected tenant population, though, locating the MMR on an exterior wall and even near a loading dock could be a deal breaker for security reasons. If your expected tenant population requires significantly more security than normal commercial businesses, the MMR should not act a main point of entry but should instead be placed within the data center, away from external walls.

Although some standards exist, the business uses of the operators and tenants will dictate the type of cross-connect being employed. Each method has challenges in a colo facility, and each challenge can be met so long as they are identified early and planned for.

meet me room adalah koli

While not a complete list, the most common connection methods are as follows: Direct connect—Here each carrier connects directly with the client from the carrier-equipment rack in the MMR to the client-side demarcation point or equipment rack, which is also located in a secure half of the MMR see figure, illustration 1.

The tenant then extends to the floor space. In this scenario the MMR is split for security reasons between tenants and carriers.

Carrier-Neutral Meet-Me Rooms for the Data Center

Tenants are permitted in their side of the MMR, and carriers in theirs. As with other options, this approach could increase the amount of conduit in the ceiling space and quickly limit future installs. Additionally, it could pose a security concern to all building tenants. Using a third-party cross-connect provider as the only staff permitted in the customer side of the MMR should limit these concerns.

Direct connect—extended demarcation—This means each carrier connects directly with the client from the carrier-equipment rack in the MMR to the client-side demarcation point in the tenant space see figure, illustration 2. In this scenario the multiple conduits demanded by tenants can quickly fill any available space above the ceiling.

meet me room adalah koli

Consider using flexible armor cable as an alternative to rigid conduit. Although some tenants want this service, some do not. Cross-connect in the MMR—In this scenario, each tenant space has pre-installed patch panels located in a secure side of the MMR whereby multiple carriers cross-connect see figure, illustration 3.

PTS Partner NJFX A Carrier Neutral, Meet Me Room in a Cable Landing Station

Some tenants may express security concerns with this topology, and carriers may not like the potential that a competitor could accidently unplug their patch. If the MMR is professionally managed which is highly recommendedhowever, the carrier would not have access to this side of the MMR, ameliorating this concern. Drawbacks include higher upfront costs to carriers and operators, who may never connect to every tenant, and loss of operator cross-connect fees, again assuming that charging for cross-connections is part of the business model.

The MMR cannot be viewed as a free space for carriers and tenants to cross-connect at will.

The best method of managing the MMRs is to create in-building standards and include them in every lease agreement. Additionally, carrier agreements should include adherence to your standards. These standards need to outline access-control, cross-connect, interconnect, and direct-connection means and methods, as well as installation and pathway standards, cable count and color standards, and labeling criteria.

Examples of a few of these in-building standards include the following: Access control—Control access to carrier sides and, if designed, tenant sides of the MMRs. Only permit third-party MMR management companies to have access to both rooms.

Meet-me room

Make sure this access is authorized, authenticated and audited. This may not sound like something that occurs, but it certainly does. Most cities have companies offering this service, and if not, a good cable installer can be assigned to the task of managing the MMR as long as the standards are well documented and SLAs between that company and the operator exist.

Direct Connect Extended Demarcation Point — It means each carrier connects directly with the client from the carrier-equipment rack in the MMR to the client-side demarcation point located in the client space see figure below.

meet me room adalah koli

Multiple conduits demanded by clients can quickly fill any available space above the ceiling. Cross Connect in the MMR — Each client space has pre-installed patch panels located in a secure side of the MMR whereby multiple carriers cross-connect see figure below. The pre-installed facility is then patched to the client's equipment in the floor space.

Similar to the "Direct Connect" method, some clients may express security concerns with this topology and carriers may not like the potential that a competitor could accidentally unplug their patch.

Green Data Center Design and Management: Data Center Design Consideration: Meet Me Rooms (MMR)

If the MMR is professionally managed which is highly recommendedthe carrier would not have access to this side of the MMR. Drawbacks include higher upfront costs to carriers and operators, who may never connect to every client, and loss of operator cross-connect fees. In addition, carrier agreements should include adherence to your standards. These standards need to outline access-control, cross-connect, interconnect, and direct-connection means and methods, as well as installation and pathway standards, cable count and color standards, and labeling criteria.

Only permit third-party MMR management companies to have access to both rooms. Make sure this access is authorized, authenticated and audited. Connection Methods — A good cable installer can be assigned to the task of managing the MMR as long as the standards are well documented and SLAs between that company and the operator exist. Pathway Standards — The MMR space above the ceiling is not limitless; as such, controls must be put in place to ensure large and typically unused conduits are not positioned between data connection points.

Traditional cable tray is a sure means of transporting media; most clients will claim that cable trays are an inherent security risk, however. The use of flexible armored cable is something all operators should consider.

It is lightweight, able to bend and ultra-thin compared with conduit. Color Codes — Color coding the media is a best practice for many reasons. Colors can designate fiber-types, counts, installation dates and specific client connections. Mining out the infrastructure of past clients is easy once the cables are identified, and identification by color is a quick means of disposal. For details of the MMR and structured cabling system design copper and fiber cablesplease consider to attend a credential program and further learning for telecommunications spaces, horizontal and backbone distribution systems.